Fire Drill Requirements in Healthcare Facilities

Fire drills are one of the simplest Life Safety requirements and one of the most frequently cited, because facilities miss a shift, run every drill at the same time of day, or keep records that do not show what happened. The requirement comes from the Life Safety Code as adopted by CMS and is reinforced by every accrediting organization.

By Brandon Deaver, CHFM · Updated October 14, 2026

The purpose of the drill is to confirm staff can perform their fire response duties, not to evacuate patients. Surveyors read the drill records and then ask staff on the floor to describe their role.

Health care occupancies: hospitals, nursing facilities, inpatient rehabilitation

  • Fire drills quarterly on each shift
  • Drills conducted at unexpected times and under varying conditions
  • Between 9:00 p.m. and 6:00 a.m., a coded announcement may be used instead of audible alarms
  • Staff trained in the fire plan and their specific duties, with transmission of the alarm, containment, extinguishment and evacuation to a smoke compartment

Ambulatory health care occupancies: surgery centers

  • Fire drills quarterly on each shift
  • Staff instructed in the fire plan and their duties
  • Drills may be announced in advance to protect patients undergoing procedures

What the drill record should show

  • Date, time and shift
  • Location and simulated fire scenario
  • Alarm transmission and response time
  • Staff who participated and their performance
  • Deficiencies identified and corrective actions
  • Signature of the person conducting the drill

Common citations

Missing drills on the night shift, four drills a year all at 10:00 a.m., records with no critique and no staff names, and staff who cannot describe the fire plan when asked. Each is correctable with a drill calendar by shift and a standard record form.

Frequently asked questions

One per shift per quarter. A hospital running three shifts needs twelve drills a year, spread across all shifts.